Power up
Battery supply
¨
A battery lead supplied in the spares pack must be
fitted to the Power supply board, connector P7 labelled
Bat1. Next install the batteries inside the enclosure,
which requires removal of battery brackets from the
panel and installation of the batteries in correct
orientation, standing on the small side with terminals at
the top facing outwards. Secure the batteries by
refitting the battery brackets.
¨
Switch On the mains supply to the panel and then
make the connection to the battery.
"
The panel makes use of sealed lead acid type
batteries which can have a useful life of up to 5 years
from the date of manufacture. It is strongly recommended
that batteries are replaced after 4 years of use. Batteries
must be disposed of as per recommendation made by
battery manufacturer.
&
Always use the recommended
replacement battery. As there is a risk of an
explosion if incorrect batteries are used.
Mains supply
¨
Ensure the mains supply cable enters the equipment via
a dedicated cable entry point, which is located adjacent
to the mains terminal block and is also segregated from
any loop wiring.
¨
The mains supply to the fire alarm control and
indicating equipment must be via a 2-pole unswitched
fused spur unit (Disconnect device).
A Disconnect Device should be available as part of the
building installation, fitted near the panel. The contacts
of the disconnect device should have a separation of at
least 3mm.
&
Hazardous voltage remains after
operation of a protection fuse. Take appropriate
action to guard against the risk of equipment having
exposed live mains supply.
¨
Each fire alarm equipment fused spur unit must be
from a dedicated switch or protective device at the
local mains supply distribution board, which should be
clearly labelled FIRE ALARM - DO NOT SWITCH
OFF.
Indicators on the power supply board
Description Y1
(yellow)
Y2
(yellow)
G1
(green)
Normal condition
(no faults in the
system)
fast flash
Mains out of limit slow flash
24VDC failure only fast flash fast flash
Battery 1 failure
only
slow flash fast flash
Battery 1 and
24VDC failure
slow flash fast flash
43VDC failure only fast flash fast flash
No power to PSU
Earth fault only On On On
Note on initial power up all three LEDs on the PSU
will switch on for approximately 1 second duration.
Generic Commissioning instructions
36 4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Vigilon Compact Voice Alarm Panel
Black
Red
2 - 12V 12Ah battery
P3
43V
FS6
1A
24V FS4 - 1A
P7
BAT1
Bat1 - FS1 - 3.15A
+
-
Y1 Y2 G1
PANEL
PSU BOARD
-
+
-
+
PANEL
Dedicated mains supply
from consumer unit
5A Unswitched fused
spur unit
P2
N
E
L
FS3 3.15A(T)
Mains fuse
DANGER
Battery brackets
Secured with two nuts
B
attery
l
ea
d
connect
i
on
on PSU board P2 Bat1
Battery brackets
Secured with two screws
Panel with doors open
PSU