EasyManua.ls Logo

Honeywell Gent Viglion EN54 - Safe Addressing; To Safe Address a Device; To Convert from Safe to Soft Address

Honeywell Gent Viglion EN54
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safe Addressing
A safe address is an address given to a devices during
commissioning, the value of which is stored in the non volatile
memory within the electronics module of the device, the Safe
address is therefore carried with the device.
A Safe address can be given to any device on loop circuit:
¨
Individually
¨
in a consecutive range
¨
or an entire loop can be safe addressed
To safe address a device
Press Menu On/Off button and then [Set Up] and then
momentarily press <etc> to select [Set Up] and then
momentarily press <etc> to select [Device], now type in the soft
address of the device and then select [Loop], now type in the
loop on which the device resides and then select [Safe] and
finally type in a safe address and select [Enter].
"
It is efficient to safe address devices using the
commissioning tool. If safe addressing a range of devices
it is quicker to do using the controls at the panel.
To convert from safe to soft address
If for any reason the safe address given to a device is not
required and the device needs to be converted for soft
addressing, then:
Press Menu On/Off button and select [Set Up] and then
momentarily press <etc> to select [Set Up] and then
momentarily press <etc> to select [Device], now type in the
safe address of the device and then select [Loop], now type in
the loop on which the device resides and then select [Safe] and
finally type in 0 the safe address and select [Enter]. This will
convert the device back to soft addressing mode.
Generic Commissioning instructions
46 4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Safe Addressing
Map information for Loop 2
Os Prev Next Common Position
+1 End1 2 Main Loop
+2 1 3 Main Loop
+3 2 4 Main Loop
+4 3 9 L2 5 Spur Loop
+5 4 6
+6 5 7
+7 6 8
15:45
Spur Loop
Spur Loop
Spur Loop
Spur Loop
+ indicates
the device
is safe
addressed

Table of Contents