Exception (or Condition) Codes for S-Quads
Gen
type
Pos
No. Description
Exception codes
normal
band
sub fault band fault band
01 2 3
E
N
V
I
O
R
N
M
E
N
T
1st Optical
subfire
None Small signal
sensed
[Check
location, state
& type]
Subfire
[Check location,
state & type]
2nd Heat subfire None Small signal
sensed
[Check
location, state
& type]
Subfire
[Check location,
state & type]
3rd
Gas subfire
- Small signal
sensed
[Check
location, state
& type]
Subfire
[Check location,
state & type]
4th -
S
E
N
S
O
R
5th Optical/Gas
channel drift
or out of
range
OK Close to
acceptable limit
Out of limits
[Clean/replace]
6th Heat channel
drift or out of
range
OK Out of limits
[Clean/replace]
7th Optical/Gas
channel
noisy (High
freq)
OK Single HF
noise event
detected
Multiple HF
noise seen
(Check location
and report)
8th Heat channel
noisy (High
frequency)
OK Single HF
noise event
detected
Multiple HF
noise seen
(check location
and report)
D
E
V
I
C
E
9th device
firmware
OK Isolated fault
[Note/report]
Repetitive fault
[Note/report/
replace]
Total failure
[Replace]
10th device
transmission
OK Low error rate Medium error
rate
[Report]
High error rate
[Replace]
Generic Commissioning instructions
56 4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Device checks