Mini-AT User Guide
Item
No. Item Name Description
————————————————————————————————————————
174 REPORT TRIGGER 10 When activated, this trigger will cause an audit trail entry to time-
stamp Alarms Cleared, either manually or automatically by RBX.
The Clear Alarm action will also provide an alarm output pulse and
change item 176 (RBX ALARM EVENT) from “00000000” to
“11111111” if item 165 (RBX ALARM ENABLE) is set to RBX
Alarms (code 1).
Select: 0 - Inactive
1 - Activated-----Default
175 REPORT TRIGGER 11 When activated, this trigger will cause an audit trail entry to time-
stamp instrument Shutdown.
Select: 0 - Inactive
1 - Activated-----Default
176 RBX ALARM EVENT This item provides an indication of RBX alarm activity since last
interrogated. It normally displays “00000000” and is internally set
to “11111111” when any alarm becomes activate or is cleared. It
must be externally resetto “00000000” after each interrogation (if
needed) to determine the status of future changes.
Default = 00000000
177 PULSE REPETITION The amount of time (in hours) an alarm pulse will be PERIOD
retransmitted if the current alarm(s) have not been acknowledged
(read). Setting this item to “0” will disable this feature. Integer
values only, fractions are not allowed.
Range: 0 to 24 Default = 24
183 PREV DAY CORVOL Yesterday’s Daily Corrected Volume, i.e., the daily corrected
volume that is one ‘Gas Day’ old at the time the instrument was
accessed. This information is updated with the value from item
223 at the beginning of every new gas day. Note: The gas day
begins at the time entered at item 205.
Default = 00000000
184 PREV DAY UNCVOL Yesterday’s Daily Uncorrected Volume, i.e., the daily uncorrected
volume that is one ‘Gas Day’ old at the time the instrument was
accessed. This information is updated with the value from item
224 at the beginning of every new gas day. Note: The gas day
begins at the time entered at item 205.
Default = 00000000