Mini-AT User Guide
Item
No. Item Name Description
————————————————————————————————————————
215 PCOR INTVL LO P Lowest PCor Gas Pressure (item 008) measured during the Time
interval selected at item 202. The value at item 214 is initialized
(re-zeroed) at the beginning of each new log interval.
Default = 099999.99
216 INTVL HI TEMP Highest Gas Temperature (item 026) measured during the Time
interval selected at item 202. The value at item 214 is initialized
(re-zeroed) at the beginning of each new log interval.
Default = -40.00
217 INTVL LO TEMP Lowest Gas Temperature (item 026) measured during the Time
interval selected at item 202. The value at item 214 is initialized
(re-zeroed) at the beginning of each new log interval.
Default = 099999.99
218 INST DIAL RATE “Instantaneous” meter flow rate derived from the UncVol meter
pulses and expressed in Cubic Feet per hour or Cubic Meters per
hour (depending on the selection at item 098). Similar to INST
FLOW RATE (item 209), including the 1-minute time limitation.
Default = 0.00
219 PEAK DIAL RATE Highest value of item 218 during the current log interval. Similar
to PEAK FLOW RATE (item 210).
Default = 0.00
220 NOMINATED CORVOL The nominated daily contract volume, with the value entered using
the selected CorVol units (item 090). When the value for DAILY
CORVOL (item 223) reaches the NOMINATED CORVOL (item
220), a time-stamp record is placed in audit trail memory, if item
236 is enabled.
Default = 99999999
221 DAILY CORVOL LIMIT High limit for daily contract volume
, initiates an alarm (item
222) if exceeded
Default = 99999999