MORLEY-IAS Dimension Series
Page 14 Document No. 996-148-000-5, Revision: 5 User Manual
To view other zones in a fault condition (or to return to the main display), press the Ï Ð keys.
EN54
9
EN54-2 8.3
Fault Signals from
points.
To view the devices (points) in a fault condition, press the Î key. The
display then shows the first point in a fault condition in the selected
zone. For example:
FAULT 01/02 Z01 L1 A010 OPT 12:19
NO REPLY FROM DEVICE:back R:more :text
The display shows the fault number and the total number of devices (points) in a fault condition in this
zone (01/02), the Zone number (Z01), the loop number to which this device is connected (L1), the
address of this device on the loop (A010), the type of device (OPT), the time at which the device
entered the alarm condition (12:19) and a description of the fault.
To view other points in fault in this zone, press the Ï Ð keys (Note: The ‘R: more’ option is not shown
if there is only one event, the and ‘’ keys are shown for the first and last entries in the list).
To return to the list of zones in fault, press the Í key.
To view the location texts for this device press the Î key. The display then shows the Zone Location
Text and the Point Location Text (20 character description each) for this device. For example:
FAULT 01/02 Z01 L1 S010 OPT 12:19
<Zone-Location-Text><Point-Location-Txt>
To return to the previous display, press the Í key.
4.2.3 Test Conditions
EN54
9
EN54-2 10
Test Condition.
If zones have been configured to be in a test condition (i.e. weekly
walk test), the TEST LED is illuminated.
To view the zones in a test conditions use the navigation keys as follows.
Press the ÍÏÐÎ keys to select the TEST option and then press the
9 key and the display shows
further information on the faults. For example:
IN TEST ZONE 1 01/02 WITH SOUNDERS
<Zone-Location-Text> :back R:More Zones
IN TEST ZONE 2 02/02 NO SOUNDERS
<Zone-Location-Text> :back R:More Zones
The display shows the Zone number and Zone Location Text (20 character description) of the first
zone in a test condition. It also indicates whether the sounders / bells will ring briefly when a device in
the zone is tested.
To view other zones in a test condition press the Ï and Ð keys.
To return to the previous display, press the Í key.