Dimension Series    MORLEY-IAS 
 
User Manual  Document No.996-148-000-5, Revision: 5  Page 37 
6  Delayed Day Mode Operation 
•  The panel can be configured to operate in a delayed day mode during the daytime for any specified 
zone. 
•  During this time, high sensor signals received from a detector will generate a fire alarm message on 
the panel but delay the ringing of the sounders. The panel will initiate a full fire alarm condition if no 
action is taken on this warning within a specified period. 
•  If a second device indicates a fire alarm (from the same or another zone), the delayed day mode 
function will be overridden and the panel will initiate a full fire alarm condition immediately. 
•  The use of delayed day mode must be configured at Level 3 by an installer / maintenance contractor 
before it is available for use at Level 2. 
•  The delayed day mode can be configured to only operate at specified times of the day. The maximum 
time allowed acknowledging stage 1 and stage 2 times can be programmed in intervals of one second. 
•  While the Delayed Day Mode Function is in the active period the Delayed Mode LED will be 
illuminated. 
6.1 Stage 1 
•  When a fire alarm condition is detected during delayed day mode, the internal buzzer will sound. The 
sensor location (including zone location and point location text) will be shown on the display along with 
a warning that the panel has entered stage 1 of a delayed alarm. The time remaining to acknowledge 
the alarm is indicated and counts down from the programmed limit. 
 
FIRE STG 1  01/01  Z01 Stage 1 TIME : 30s 
<Zone-Location-Text><Point-Location-Text> 
 
•  The lower line of the display cycles through the following messages every second. 
 
<Zone-Location-Text><Point-Location-Text> 
 
Press X to view Faults/Disablement/Test 
 
Press ACCEPT key to start stage 2 timer 
 
•  If the warning is not acknowledged, by pressing ACCEPT, within the time allowed for stage 1, then a 
full fire alarm condition will be raised and the sounder outputs will activate.  
• Press ACCEPT within the time allowed to enter the stage 2 (investigation phase) of the delayed 
alarm. 
• Press MUTE BUZZER to silence the internal buzzer. 
•  If required, press ‘X’ to return the display to the normal display indicating the number if fires, faults, 
disablements and test conditions. The details of other conditions can now be viewed.