Dimension Series MORLEY-IAS
User Manual Document No.996-148-000-5, Revision: 5 Page 19
4.3.2.4.1 Panel Disablements
D
ISABLE ALL SOUNDERS 01/03 12:15
In the example above, the display shows a description of the event, the event number and the total
number of events and the time at which the event (sounders disabled) was programmed (12:15).
Press the ÏÐ keys to scroll though the event list manually. If no key is pressed for 60 seconds, auto-
scrolling will resume.
4.3.2.4.2 Zone Disablements
DISABLE FULL ZONE 02/03 Z01 03:36
In the example above, the display shows a description of the event, the event number and the total
number of events, the zone that is disabled and the time at which the event (zone disabled) was
progammed (03:36).
Press the ÏÐ keys to scroll though the event list manually. If no key is pressed for 60 seconds, auto-
scrolling will resume.
4.3.2.4.3 Point disablements
Example :
DISABLED 09/10 Z01 L1 A054 MCP 09:34
<Zone-Location-Text><Point-Location-
T
xt>
In the example above, the display shows a description of the event, the event number and the total
number of events, the Zone number (Z01), the loop number to which this device is connected (L1),
the address of this device on the loop (A054), the type of device (MCP) and the time at which the
device was disabled (09:34)
The bottom line shows the Zone Location Text (20 character description) and the Point Location Text
(20 character description) for this device.
Press the ÏÐ keys to scroll though the event list manually. If no key is pressed for 60 seconds, auto-
scrolling will resume.
4.4 Power Supply Fault Conditions
If the AC MAINS power source is interrupted or if the panel registers other fault conditions associated
with its power supply, the Supply Fault LED and Fault LED Indicators will be lit. Further details of the
fault can be viewed on the display.
The back light illumination of the alphanumeric display will be turned off.
If both the AC MAINS input and the Battery Standby Input fail then all LED and alphanumeric display
indicators will be off.
Possible fault conditions are: