Dimension Series    MORLEY-IAS 
 
User Manual  Document No.996-148-000-5, Revision: 5  Page 19 
4.3.2.4.1 Panel Disablements 
 
ISABLE ALL SOUNDERS  01/03          12:15  
 
 
•  In the example above, the display shows a description of the event, the event number and the total 
number of events and the time at which the event (sounders disabled) was programmed (12:15).   
• Press the ÏÐ keys to scroll though the event list manually. If no key is pressed for 60 seconds, auto-
scrolling will resume. 
4.3.2.4.2 Zone Disablements 
 
DISABLE FULL ZONE      02/03  Z01   03:36 
 
 
•  In the example above, the display shows a description of the event, the event number and the total 
number of events, the zone that is disabled and the time at which the event (zone disabled) was 
progammed (03:36).   
• Press the ÏÐ keys to scroll though the event list manually. If no key is pressed for 60 seconds, auto-
scrolling will resume. 
4.3.2.4.3 Point disablements 
 
Example : 
 
DISABLED     09/10 Z01 L1 A054 MCP 09:34 
<Zone-Location-Text><Point-Location-
xt>   
 
•  In the example above, the display shows a description of the event, the event number and the total 
number of events, the Zone number (Z01), the loop number to which this device is connected (L1), 
the address of this device on the loop (A054), the type of device (MCP) and the time at which the 
device was disabled (09:34)  
•  The bottom line shows the Zone Location Text (20 character description) and the Point Location Text 
(20 character description) for this device. 
• Press the ÏÐ keys to scroll though the event list manually. If no key is pressed for 60 seconds, auto-
scrolling will resume. 
4.4  Power Supply Fault Conditions 
•  If the AC MAINS power source is interrupted or if the panel registers other fault conditions associated 
with its power supply, the Supply Fault LED and Fault LED Indicators will be lit. Further details of the 
fault can be viewed on the display. 
•  The back light illumination of the alphanumeric display will be turned off. 
•  If both the AC MAINS input and the Battery Standby Input fail then all LED and alphanumeric display 
indicators will be off. 
•  Possible fault conditions are: