User Manual Document No.996-148-000-5, Revision: 5 Page 13
To view other points in fire in this zone, press the Ï and Ð keys (Note: The ‘R: more’ option is not
shown if there is only one event, the ‘’ and ‘’ keys are shown for the first and last entries in the list).
To return to the list of zones in fire, press the Í key.
4.2.1.3 Override Delays
EN54
9
EN54-2 7.11d
Override delays at
Level 1
The DX1e, DX2e and DX4e control panels can be
configured to operate with delays to outputs. In this
case, a manual call point (MCP) will be located next
to the panel.
To override any delays and immediately activate the
bells and other fire alarm output devices, break the
glass in the call point.
BREAK GLASS
Press Here
FIRE
4.2.2 Fault Conditions
If the panel detects a fault, the FAULT LED is illuminated along with other appropriate system
condition LED Indicators. The internal buzzer will sound and the alphanumeric display will indicate the
number of faults.
To view more detailed information regarding the fault locations use the navigation keys as follows.
Press the ÍÏÐÎ keys to select the FAULT option and then press the
9 key. The display shows
further information on the faults. For example:
TOTAL PANEL FAULTS :3 :Panel Events
TOTAL ZONES IN FAULT :1 :Zone Details
This display indicates that there is one zone in fault and that three panel related faults have been
registered. To view these, press the Î key to view the panel related faults and press the Ð key to
view the zones in fault.
4.2.2.1 Panel Faults
FAULT 02/03 MON INPUT 1 12:15
INPUT OPEN CIRCUIT :back R:more
The above example shows there are three panel related faults and fault number two is shown. This
was an input open circuit on “Monitored Input 1” registered at 12:15PM.
If there is more than one fault indicated, use the Ï and Ð keys to view these (Note: The ‘R: more’
option is not shown if there is only one event, the ‘’ and keys are shown for the first and last entries
in the list). Press the Í key to return to the main display.
4.2.2.2 Zone Faults
When selected, the display shows the first zone with a fault condition. For example:
IN FAULT ZONE 1 01/01 R: More Zones
<Zone-Location-Text> :Device Details
The display shows the Zone number and Zone Location Text (20 character description).