Dimension Series MORLEY-IAS
User Manual Document No.996-148-000-5, Revision: 5 Page 25
5.3.1.4.1 Internal Outputs
• To select the option, press ‘1’ and the display shows to first available panel output circuit as follows:
[Internal Test] B:01 Sounder 1
9:Start Test R:Select Output X:Exit
• Press the Ï and Ð keys to select the required output. A full list of available outputs is detailed in the
table below:
• To start a test on the device and turn the output on, press the ‘
9’ key. The display then shows:
[Internal Test] B:01 Sounder 1
Output test in progress X:Stop
• Press the ‘X’ key to stop the test.
Type of Output
Sounder Output 1
Sounder Output 2
Fault Relay
Fire Relay
Programmable Relay
Table 6 – Panel Internal Output Circuits
5.3.1.4.2 Loop (SLC) Outputs
• To select the option, press ‘2’ and the display shows to first available loop output circuit as follows:
[SLC Test] A008 SDR
9:Start Test R:Select Output X:Exit
• Press the Ï and Ð keys to select the required output. The display shows the address of the device
(i.e. A008) and its type abbreviation code (i.e. SDR).
• To start a test on the device and turn the output on, press the ‘
9’ key. The display then shows:
[SLC Test] A008 SDR
Output test in progress X:Stop
• Press the ‘X’ key to stop the test.
• Note that if the panel is equipped with 2 or 4 loops then the display will first prompt for selection of the
required signalling / detection loop.