MORLEY-IAS Dimension Series
Page 28 Document No. 996-148-000-5, Revision: 5 User Manual
NOTE: On entry, the display may indicate that the zone is ‘Part Disabled’. This is because one or more
devices / points have been disabled individually. This zone disable / enable function will only
FULLY Disable the zone or will re-enable the zone to the partial disablement condition (the
panel remembers those devices that are individually disabled).
5.3.5.2 Disable / Enable Individual Devices / Points
EN54
9
EN54-2 9.5
Disablement of
each addressable
point.
• Individual detection devices can be disabled.
• To disable or enable a device, press ‘2’ and the display shows the
first available device and its current enable / disable state. For
example:
[device address text ] A010 Enabled
←→Change R:More devices X:Exit
• Note that if the panel is equipped with 2 or 4 loops then the display will first prompt for selection of the
required signalling / detection loop.
• Press the Í or Î keys to change the enable/disable state of the device. The new status is shown on
the display as “Enabled” or “Disabled” as appropriate.
• Press the Ï and Ð keys to select a different device. (Note: The display will only show devices that are
connected to the panel).
• Press ‘X’ to return to the enable / disable menu.
NOTE: A zone will only be fully enabled / disabled if all of the devices within the zone are enabled / disabled.
NOTE: Sounder type outputs can only be disabled using this option if this function has been configured
during panel commissioning.
5.3.5.3 Disable / Enable Groups
• A number of devices may have been configured to belong to a group. This function allows all of the
devices within this group to be disabled / enabled with one action rather than having to disable /
enable each individual device.
• To disable or enable a group of devices, press ‘3’ and the display shows the first available group and
its current enable / disable state. For example:
[Disable/Enable] Group 1 Enabled
←→Change R:More Groups X:Exit
• Press the Í or Î keys to change the enable/disable state of the group. The new status is shown on
the display as “Enabled” or “Disabled” as appropriate.
• Press the Ï and Ð keys to select a different group. (Note: There are two groups available).
• Press ‘X’ to return to the enable / disable menu.
NOTE: A zone will only be fully enabled / disabled if all of the devices within the zone are enabled /
disabled. The devices included in a group are programmed in the commission menu options.
NOTE: Sounder type outputs can only be disabled using this option if this function has been configured
during panel commissioning.
5.3.5.4 Disable / Enable Specific Output Circuits
EN54
9
EN54-2 9.4.1c
EN54-2 9.4.2a
Disablement of
outputs.
• It is possible to disable outputs to fire alarm devices (sounders / bells)
independently.
• It is possible to disable the fault output independently.
• It is possible to disable other outputs independently.