User Manual Document No.996-148-000-5, Revision: 5 Page 29
• To disable or enable a type of output circuit, press ‘4’ and the display shows a menu of the types of
outputs. For example:
[U0 Disable/Enable] 1:Sounders
2:Fault Relays 3:Others
• It is possible to enable or disable:
1. ALL Sounder Type Outputs.
2. ALL Fault Relay Type Outputs.
3. ALL Other Relay and Control Type Outputs
• NOTE: The ‘Sounder’ device setting is used to differentiate between Sounder Type Outputs and
Other/Control Type Outputs. Refer to the Product Manual for more information.
• Press ‘1’, ‘2’ or ‘3’ are as required. The display then shows the following if the outputs are currently
enabled.
Disable ALL Sounder Outputs
Press 9 to Confirm X:Cancel
Disable ALL Fault Relay Outputs
Press 9 to Confirm X:Cancel
Disable ALL Relay and CTL Outputs
Press 9 to Confirm X:Cancel
• The display shows the following if the outputs are currently disabled.
Enable ALL Sounder Outputs
Press 9 to Confirm X:Cancel
Enable ALL Fault Relay Outputs
Press 9 to Confirm X:Cancel
Enable ALL Relay and CTL Outputs
Press 9 to Confirm X:Cancel
• Press the ‘
9’ key to confirm the enable / disable action and return to the enable / disable outputs
menu.
• Press ‘X’ to return to the enable / disable outputs menu without making a change.