Dimension Series    MORLEY-IAS 
 
User Manual  Document No.996-148-000-5, Revision: 5  Page 41 
9  Level 3 Programmer Functions 
•  Refer to the Product Manual (996-147) for complete information on installation, commissioning and 
programming the DX1e, DX2e and DX4e Fire Alarm Control Panels. 
10 Maintenance / Inspection 
 
 
BS5839 
! 
 
BS5839-1: 2002 
Clauses 45 & 47 
Inspection, Service and 
User Responsibilities. 
•  The Equipment Owner shall ensure that a periodic Inspection 
and Servicing Maintenance Schedule be followed. The 
implementation of a maintenance contract with a 3
rd
 party 
approved Fire Alarm Service and Maintenance Company is 
recommended. 
•  The aim is to provide a complete check and test of the entire 
fire alarm system within a 12-month period. 
•  The Equipment Owner shall appoint a single, named 
Responsible Person to oversee all aspects related to the fire 
alarm system, including record keeping, testing and false alarm 
management. Refer to the standard for a complete list of the 
Responsible Person’s recommended duties. 
 
•  In accordance with best practice, the Responsible Person should maintain a logbook to record all 
events resulting from or affecting the system. The logbook should be kept in a place accessible to 
authorized persons (preferably near the main panel). 
•  All events should be properly recorded (events include real and false fire alarms, faults, pre-alarm 
warnings, tests, temporary disconnection’s and service visits). A brief note of any work carried out or 
outstanding should be made. 
10.1  Inspection / Testing 
•  It is recommended that the Responsible Person undertake the following test schedule. 
10.1.1 Daily Attention  
•  Check the following: 
1.  The panel should indicate normal operation & if not the fault should be recorded in a logbook & reported 
to the servicing organization. 
2.  Any faults previously reported have received attention. 
10.1.2 Weekly Attention 
•  Check the following: 
1.  Every week, at approximately the same time each week, a manual call point should be operated during 
normal working hours. Check that the system responds to the fire alarm and turns on appropriate alarm 
outputs. Where permissible, any link to the fire brigade or remote manned centre should also be operated. 
2.  A different manual call point shall be used each week so that ALL manual call points are exercised in 
rotation. 
10.1.3 Monthly Attention 
•  Check the following: 
1.  Any stand-by generators should be started and fuel levels checked.