MORLEY-IAS Dimension Series
Page 36 Document No. 996-148-000-5, Revision: 5 User Manual
5.3.6.7 View Voltages
• Press ‘7’ to select the View Voltages option. The display initially shows the voltage across the battery.
For example:
[U0 VOLTS] BATTERY VOLTS = 23.6
R:Select X:Exit
• Press the Ï and Ð keys to view other readings (see table below for full list of signals that can be
viewed and their normal values). For example:
[U0 VOLTS] CHARGER = 26.5
R:Select X:Exit
• Press ‘X’ to return to the View menu.
Signal Description Value Normal
Reading /
Range
BATTERY VOLTS Measurement of the Battery Voltage Volts 24 (19-28)
CHARGER Measurement of the Charger Output Voltage Volts 27 (20-29)
AC POWER Measurement of the AC Power Input Volts 240 (190-260)
BATTERY WIRING Measurement of the battery wiring resistance
1
mOhms 350 (200-500)
MONITORED INPUT 2 Measurement of the input signal condition Count 500 (480-520)
MONITORED INPUT 1 Measurement of the input signal condition Count 500 (480-520)
SOUNDER 2 Measurement of the output wiring condition Count 190 (170-210)
SOUNDER 1 Measurement of the output wiring condition Count 190 (170-210)
EARTH Measurement of the earth condition Count 270 (240-300)
Measurement readings shown are for indicative purposes only.
1
The measurement reading depends also on battery capacity and condition.
Table 7 – Voltage / Analogue Value Readings
5.3.6.8 View Version
• Press ‘8’ to select the View Versions option. The display shows the part number and version of the
software installed in the panel. It also shows the loop driver protocol and software version loaded into
the signalling loop driver circuit. For example:
[U0 VERSION] System : 993-667-000 3.00
Loop : Apollo 6.02
• Press ‘X’ to return to the View menu.