5.3  Level 2 Menu Functions 
•  Press any number (0 – 9) key to display the Level 2 Menu Functions. These are normally inhibited 
from use and the alphanumeric display will prompt for entry of the Level 2 pass-code as follows.  
 
ACCESS TO MENUS RESTRICTED  
Enter Level 2/3 passcode,        ←:BackSp 
 
•  Enter the Level 2 pass-code, as described above, and the display will then show the Level 2 Menu 
Functions. 
•  Alternatively, if the key-switch option is fitted and programmed to enable Level 2 access, insert the key 
and turn clockwise before selecting Level 2 Menu functions. 
 
[U0]  1:Commission  2:Test  3:Clock 
     4:Disable/Enable  5:View Mode 
 
 
Function  Description 
Commission  This option is not available to Level 2 users. It requires the entry of 
the Level 3 password before the programming mode can be entered. 
Test  Allows the user to test parts of the system. The following tests can be 
performed: 
LED  To test the LED indicator lamps. This test will 
automatically test all status indicators and each zone 
indicator, in turn, and then terminate. 
LCD  To test the alphanumeric display. 
ZONES  To perform a ‘Walk Test’ on one or more zones. If the 
test is performed ‘With Sounders’ all relay and sounder 
outputs will be activated in continuous mode regardless 
of pattern logic.   
OUTPUTS  To test the relay and sounder outputs connected to the 
system. 
BUZZER  To test the internal buzzer. 
Clock  To change the date and time in the panel. 
Disable / Enable  To enable zones, inputs, outputs, delays and day mode operation. 
View  To view devices, log, faults and other system status conditions. 
Table 5 - User Menu Options 
•  The display will automatically revert to the Normal display after 60-seconds (programmable) if no 
buttons are pressed. Press any number (0 – 9) key to return to the Level 2 menu display. 
•  Access to Level 2 menu functions will automatically be cancelled after 5-minutes (programmable) if no 
buttons are pressed. It will be necessary to re-enter the pass-code to re-enable the Level 2 menu 
functions. 
• Press the ‘X’ key to manually return to the normal display and cancel Level 2 access.