116 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Releasing Applications Miscellaneous
The outputs are each set to a code appropriate for one of the three releasing phases: for example,
one code for the first alarm, a faster code when the Delay Timer activates, and a continuous tone
during releasing.
Program Program releasing zone ZR1 as follows:
ZR1 = Delay Time:15, Abort Switch:ULI, Cross Zone:YES, Soak Time:120
Map ZR1 to all inputs and outputs shown in this example.
Program logic zones as follows:
ZL1 = AND(OR(L1D1,L1D2,L1D3,L1D4,
L1D5,L1D6),NOT(L1M30))
When conditions are met for ZL1, a first alarm has occurred
in the releasing zone, but the
Delay Timer has not yet started. Map ZL1 to an output set to the code chosen for a first alarm
(L1M31 in this example).
ZL2 = AND(L1M30,NOT(L1M20))
When conditions are met for ZL2, the Delay Timer h
as started, but releasing has not begun.
Map ZL2 to the output set to the code chosen for when the Delay Timer activates (L1M32 in
this example).
ZL3 = OR(L1M20)
When conditions are met for ZL3, the 120
second releasing operation has begun. Map ZL3 to
the output that produces a continuous tone (L1M33 in this example).
Program output Type Codes as follows:
L1M20 = RELEASE CKT, L1M30 = INST RELEASE, L1M31 = CONTROL, L1M32 = CONTROL, L1M33 = CONTROL
Illustration
Figure B.19 A Release Code Bell Circuit
Configuration
B.4 Miscellaneous
B.4.1 Initiating Devices
Releasing zone initiating devices include the following:
FST-851/751 intelligent heat detectors
FSI-851/751, FSP-851/751, FAPT-851/751, FSL-751int
elligent smoke detectors
Conventional detection UL-listed devices connected to monitor modules
ZR01
L1D1
L1D2 L1D3 L1D4 L1D5 L1D6
L1M20 L1M30 L1M31 L1M32
Type Code
RELEASE CKT
Type Code
INST RELEASE
Type Code
control
Type Code
control
ZL1
ZL2
ZL3
L1M33
Type Code
control