76 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Alter Status Walk Test
Figure 4.8 Clear History Screen
Soft Keys
ALARM HISTORY: Press to clear Alarm
history.
EVENT HISTORY: Press to clear Event
history.
ALL HISTORY: Press to
clear both Alarm and Event history.
4.6 Walk Test
Walk Test allows the user to test the entire fire alarm system while away from the control panel.
There are two types of Walk Test - Basic and Advanced - and each type operates in audible mode.
Walk Test results are sent to the printer and to Event
History as “Test”. In Network applications,
specific nodes can be excluded from having the ability to force the fire panel out of Walk Test. This
is programmable via VeriFire Tools. Refer to the VeriFire Tools help file.
IMPORTANT!
• Prior to Walk Test, secure all protected building
s, and notify the building owner/operator,
fire department, and other pertinent personnel that testing is in progress.
• Immediately after Walk Test is completed, notify the same people that testing is complete
and the
system is restored to normal operation. Reconnect releasing devices.
• Walk Test will “time out” and return to normal operation after one hour when
no Walk Test
activations have occurred during that time.
• Walk Test may be exited at any time by pressing the ABORT soft
key on the screen.
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A TUE JAN 25, 2011
CLEAR HISTORY
ALARM HISTORY
EVENT HISTORY
ALL HISTORY
BACK
WARNING:
PHYSICALLY DISCONNECT ALL RELEASING DEVICES BEFORE STARTING WALK TEST. IT IS
NOT SUFFICIENT TO DISABLE IN ANY OTHER MANNER.
WARNING:
WALK TEST MODE CAN DEACTIVATE FIRE PROTECTION. OBSERVE THE FOLLOWING
IMPORTANT PRECAUTIONS.