12 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
General Information Basic Procedure
Pressing an ACCEPT soft key will save the information entered on the screen. It may also return to
the previous screen and/or perform other functions as described in the soft key section for each
screen.
When the FACP can not read an address (that is, if the
point entered on the screen for processing
does not exist) it will display an error screen for several seconds, then return to the screen where the
address was entered. The user must check his input and investigate the state of the point.
1.6 Basic Procedure
For initial programming of the panel, or for major changes and additions, the following basic
procedure is recommended to prevent errors resulting in reprogramming and wasted time.
Use work sheets to record the exact information for every detector, module, annunciator point
and software zone
in the system. Pay close attention to the Software Type IDs. For voice
systems, pay close attention to AMG annunciator point commands. The panel program may
also be created using VeriFire™ Tools and downloaded to the panel after assembly and power-
up.
Assemble and apply power to the control panel as described in this panel’s installation manual.
All
system boards must be physically installed.
Read this manual before programming.
Enter/change master and user passwords.
Enter panel and network parameters.
Program all devices and thoroughly test the entire system. The W
alk Test feature can be used to
test devices and their programming.
Make a hard-copy record of the program on the printer.
Save the program by uploading it using VeriFire™ Tools.
1.7 Getting Started
Once the system has been physically installed, programming may begin. The user may program at
any time except while there is an unacknowledged alarm present.
To ensure security, passwords should be entered at this time to rep
lace the factory default settings.
1.7.1 Password Change
The NFS2-3030 has two password levels; master and user. There is one master password, which
grants access to all system programming. There are nine user passwords, each of which may be
assigned access to the programming change menus, the alter status menus, or both. A user
password does not give access to or allow change to any password parameters, not even its own.
Only the master password will allow access to password change screens.
The panel arrives with factory default settings o
f 00000000 for the master password, and 11111111
for one user password.
Follow the steps below to change the
factory settings:
1. Press PROGR
AM/ALTER STATUS at the Main Menu screen.
2. Using the keyboard, enter eight
zeroes (00000000) after ENTER PASSWORD.
3. Press the ACCEP
T soft key.
4. Press the PANEL PR
OGRAM MENU soft key.
5. Press the MORE
soft key.
6. Press the PASSW
ORD CHANGE soft key.