130 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Intelligent Sensing Applications Detector Status Display
Line 14
PEAKS: 56% - This value represents the highest percent per foot obscuration reading taken by
this detector. It can be a historical figure, and does not necessarily represent the highest reading
for this particular alarm. Re-initializing the detector would reset this value to zero.
VERIFY COUNT: 02 - This displays the number of times the detector has gone into alarm.
This count aids in differentiating false alarms from actual alarms by showing repeated alarm
events that have come into the device. In this example, the detector has gone into alarm two
times since the verification count was begun. The FACP will signal a trouble condition when
the verify count exceeds 20.
CO-OP: D100,158 - Indicates the address(es) of any detector(s) linked with the detector that’s in
alarm for Co-operative Multi-Alarm Sensing. This field will not display for Acclimate detectors.
Line 15 - The current time and date are di
splayed in this line.