EasyManuals Logo

Honeywell nfs2-3030 User Manual

Honeywell nfs2-3030
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #134 background imageLoading...
Page #134 background image
134 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
CBE: Zones and Equations Equations
Example: XZONE(Z02)
If any combination of two or more initiating devices that have been mapped to
this software
zone come into alarm, then outputs mapped to this zone will activate.
The “RANGE” Operator
Each argument within the range must conform to the requ
irements of the governing function.
The range limit is 20 consecutive arguments.
Example: AND(RANGE(Z1,Z20))
Zone 1 through Zone 20 must all be active to activate the logic zone.
The “DIS(point argument)” Operator
Requires that the point argument be disabled for the operator
to go active.
The “PRE(point argument)” Operator
Requires that the point argument be in prealarm for
the operator to go active.
Example: AND(L1D1
,PRE(L1D2))
The detector at address L1D1 must be
active and the detector at L1D2 must be in prealarm for
this equation to go active.
The “SUP(point argument)” Operator
Requires that the point argument be
in an active supervisory state for the operator to go active.
Example: OR(L1D1,SUP(L1M1))
The detector at address L1D1 must be active, or the
module at L1M1 must be in an active
supervisory state, for the equation to go active.
The “FIRE(point argument)” Operator
Requires that the point argument be
in an active fire alarm state for the operator to go active.
Example: AND(L1D1,FIRE(
L1M1),FIRE(L1M2))
The detector at address L1D1 must be active, and the modules
at L1M1 and L1M2 must be in
an active fire alarm state, for the equation to go active.
The “NON(point argument)” Operator
Requires that the point argument be in an active
non-alarm state for the operator to go active.
Example: AND(L1D1,NON(L1M1))
The detector at address L1D1 must be active, and the module at a
ddress L1M1 must be in an
active non-fire alarm state, for the equation to go active.
The “SEC(point argument)” Operator
Requires that the point argument be in an active
security alarm state for the operator to go
active.
Example: AND(L1M1,SEC(L1M2))
The module at address L1M1 must be active, and the
module at address L1M2 must be in an
active security alarm state, for the equation to go active.
Time-based Functions
The panel supports three time-based functions: DEL, SDEL, and TIM. Special rules apply to an
equation containing a time-based function:
Only one time-based function may be used in an equation.
The time-based function must appear only once, as the
first entry of the equation.
It may not be nested within parentheses in the equation.
Logic functions may be used in an equation that begins with a DEL or SDEL time-based
functi
on: however, they must appear within parentheses following the time-based function.
Delay and duration times are in 24-hour format (HHMMSS); the all
owable range is 00:00:00 to
23:59:59.
The “DEL” Function

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell nfs2-3030 and is the answer not in the manual?

Honeywell nfs2-3030 Specifications

General IconGeneral
BrandHoneywell
Modelnfs2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals