Pag. 12 Programming Manual SERIEAM
NOTIFIER ITALIA Doc. M-160.2-AM-8000-ENG Rev A1 AM8000_manu-prog-ENG
DETECTORS folder
Press the right Arrow key 4 to change the time of check for the detectors:
Detectors verification time allows the control unit to perform a check for all installed sensors, for the set time,
before confirming the possible alarm.
Detectors Verification Time is programmable in seconds ( Max. 50 sec )
N.B. This function will be effective only on the enabled sensors (refer to the Point Programming menu)
Through the arrow keys select the item which is required to be changed (“Check “ or “Check Enabl.”)
through pressure of the enter key
the editing function is activated.
Through the arrow keys  data are entered and through the enter key
entered data are confirmed.
VERIFY ENABLE: selecting “YES” the verification Function is ACTIVE with the programmed verification Time (
in seconds)
SILENCE folder
SELF-SILENCING TIME is the time after which the output modules are reset, after being activated.
Press the right Arrow key 4 to change the parameters to manage the Silencing:
NOTE: the self-silencing function of each output module must be enabled in the Point Programming .
(this function is not yet implemented in the current version)
Silence Inhibit time is the time that output modules will remain active without the ability to be Silenced by an
operator.
By pressing the enter key
the editing function is activated.
Through the arrows keys  data are entered and through the enter key
entered data are confirmed.
Siren / HORN Type-ID outputs
Silence Inhibition:
Time after activation when is not possible
to Silence
Silence Autom:
Minimum activation time
Silence Autom.Enabl:
Enabling of use the Activation time
( otherways outputs are active until
Reset)
All timings are expressed in seconds,
from a minimum of 0 sec. to a max. of
255 sec.