AM_8000 Programming Manual PAGINA - 27
AM8000_manu-prog-ENG Doc. M-160.2-AM-8000-ENG Rev A1 NOTIFIER ITALIA
OUTPUT MODULES
ABBREVIATION TYPE OF DEVICE
CON
Output module with supervision of the device connection line
FORC
Output module with relay contacts free from voltage
OUTPUT MODULES FOR GENERAL SIGNALLINGS
ABBREVIATION TYPE OF DEVICE
PWRC
FORC Output module used to temporarily interrupt power supply, during SYSTEM RESET, for the 4-
wire conventional smoke sensors, powered by a remote power supply.
N.B.: this type SHALL NOT be programmed for the SILENCING
GPND FORC output module activated at each alarm or Fault
It is reset by ACK.
APND FORC output module activated at each alarm. It is reset by ACK.
GAC FORC output module activated at each alarm. It is reset by RESET.
GAS FORC output module activated at each alarm. It is reset by RESET.
TPND
FORC output module activated at each breakdown. It is reset by ACK or through the Faultelimination
GTC FORC output module activated at each breakdown. It is reset by RESET.
GTS CON output module activated at each breakdown. It is reset by RESET.
TRS
FORC output module activated at each breakdown. It is only reset through the Fault elimination.
HORN Output module activated at each alarm and follows the output state of the control unit Siren
ZDIS Output module activated in case of exclusion of a point or a zone.
MAINF Output module (non supervised output) activated when a MAINS Fault is present
MAINFC Same as MAINF but supervised output
MAINFV Same as MAINF but supervised output ( complies VDC standard )
N.B.: the output modules used for the above-mentioned functions, do not accept CBE.