Pag. 26 Programming Manual SERIEAM
NOTIFIER ITALIA Doc. M-160.2-AM-8000-ENG Rev A1 AM8000_manu-prog-ENG
Summary of SW Type-ID for modules
INPUT MODULES
CONNECTION TYPE
ABBREVIATION
TYPE OF DEVICE
MON3 Input module
Input module used for N.O. contacts
(Connection in conformity with EN54 rule).
MON Input module
Input module used for N.O. contacts or
any device
SCON MMX-2 input module
Input module used for 4- wire conventional smoke detectors
not detected during the self-programming.
N.B.: this type has a reset time which is longer than the modules programmed as “MONITOR”
SCO2 It is valid for the ZMX module for the connection of conventional sensors
It is automatically detected during the self-programming
NONA Input module
Input module used to interface with N.O. contact, with alarm when
It is closed. The activation of a “NONA” type module, does not generate an
Alarm condition, that is:
- the alarm LED is not on
- “APND” or “GPND” type modules do not activate. Only output modules coupled
to CBE are activated
PULL Like the MON device; in addition, the” MANUAL BUTTON” reading appears
STAT Input module used like the NONA device, but each state change is activated
by the buzzer, for one second.
NCMN Input module used to check the N.C. inputs
When the line is off, an alarm is indicated
In case of line short circuit, a FAULTis indicated
INPUT MODULES FOR GENERAL SERVICES
CONNECTION TYPE ABBREVIATION TYPE OF DEVICE
MTRB
Input Module used as a Tamper signalling. Through an alarm input it
signals a breakdown
MACK Input module used to perform remote ACK (pulse)
MTAC Input module used to perform remote SILENCING (pulse)
MRES Input module used to perform remote RESET (pulse)