AM_8000 Programming Manual PAGINA - 11
AM8000_manu-prog-ENG Doc. M-160.2-AM-8000-ENG Rev A1 NOTIFIER ITALIA
Programming – System - LINE
Style: OPEN LINE, CLOSED LOOP
This function allows to change (in memory) the type of line connection, according to the NFPA coding ( Open =
style 4, LOOP = style 6 ) and the scan priority of the devices connected to it.
Through a first pressure of the enter key the Line editing function is activated,
Through the arrow keys  select the line style (OPEN - LOOP)
Press the enter key
to confirm the programming.
Programming – System - Timings
In this sub-menu some delay times of the alarm outputs are programmed, the delay time for the sensor alarm
check, silencing inhibition, etc.
ALARM –OUT folder
Through the arrow keys select the item which is required to be changed (“Siren” or “Tx Alarm”)
Through pressure of the enter key
the editing function is activated.
Through the arrow keys  or through keyboard the data are entered, by pressing the enter key
you can
confirm entered data.
Sounder activation delay is programmable in seconds ( max. 600 sec)
The “Siren” and “TX Alarms” activation delay timings are active only in case of alarm if the immediate
activation of the outputs has been excluded in the exclusions menu.
The “TX Alarms” function is not implemented in this software revision.