Pag. 24  Programming Manual  SERIEAM 
NOTIFIER ITALIA  Doc. M-160.2-AM-8000-ENG Rev A1  AM8000_manu-prog-ENG
 
 
 
Where: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The  PROT 
 Protocol 
 control can dis
la
 the table of devices for one of the two 
ossible 
rotocols: CLIP or ADV
TYPE  = Type of devices found ( see table above)  
NEW = New device found 
NFO = Devices previously programmed but not coherent with what was detected during the Auto-Learn 
procedure 
TOT
 = total of devices detected on the line ( NEW + INC + correctly programmed devices.) 
MAN = Devices previously programmed but not detected during the Auto-Learn 
The CONF control saves the devices detected during the Self-Learn according to the following mode: 
-  NEW and INC  are initialised through the default data. 
-  MAN are removed 
-  The correctly programmed devices keep the current programming 
The data relevant to the initialized devices can be subsequently changed by entering the point programming 
procedure. 
  Auto-Learn  
 
 
 
 
Summar
 
Type   NEW NFO TOT MIS
PHOT     000 000 002 000 
THER      000        000        005        000 
CMA1     000 000 004 000 
MMA1     000 000 005 000 
Sample screen for CLIP detectors. 
 
Important Note :
 
 
On Each Line can be installed 
a max number of  10 device using CLIP protocol.