AM_8000  Programming Manual  PAGINA - 31 
AM8000_manu-prog-ENG  Doc. M-160.2-AM-8000-ENG Rev A1  NOTIFIER ITALIA 
Example:   G301 = TIM (   18.00  08.30)    CBE of the high sensitivity group 
 
 G302 = TIM (   08.30  18.00)    CBE of the low sensitivity group 
 
For the Detector to which this function is to be coupled the parameter “Daytime/Night = YES ”(refer to 
Detectors programming) must be programmed. In this way the system automatically associates the high and 
low sensitivity groups, so that the following two  time bands are obtained: 
 
Daytime band (low sensitivity) from 8.30 to 18. (the sensitivity values assumed by the detector are those 
programmed in the “Sens-Low” item  in the option folder). 
 
Night band (high sensitivity) from 18. to 8.30. (the sensitivity values assumed by the detector are those 
programmed in the “Sens-High”item in the option folder). 
 
  Zone Menu 
 
By selecting the “Zones” sub-menu you can enter a descriptive text  to be associated with the selected zone. 
 
The control unit locates by default on the first zone.
 
 
 
 
 
Day / Night : YES/NO 
 
Setting “YES” this Zone will use the programmed HI-LOW sensitivity Groups ( refer to HIGH AND LOW 
SENSITIVITY GROUPS above) to switch to LOW sensitivity during DAY and to HIGH sensitivity during 
the Night . 
 
 
 
 
 
Name: 
Programmable text for the ZONE 
max. 32 characters 
To enter the Text press the enter 
key
   to enter the editing function  
 
Through the alphanumerical 
keyboard enter the zone name   
at the end press the enter key   to 