116 SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012
Operating Instructions Hazard/Tornado Condition Operation
The alarm relay is not activated
Silenced alarms are not
resounded
Timers are not started
Store event in history bufferActivate appropriate LED on the N-ANN-LED annunciator
(required for this application)
Note that, like supervisories, process monitor signals latch, except when programmed for process
monitor autoresettable.
4.8 Hazard/Tornado Condition Operation
Hazard/Tornado operation is intended for Manual activation.
Hazard/Tornado Condition operation will initiate the following events:
The piezo sounder pulses ¼ second On, ¼ second Off
The LCD displays a hazard message along with the device name, type, adjective/noun,
associated zones and time/date
Communicate the hazard condition to the Central Station (if the default event code has been
changed from 000 to a reportable event code)
Relays programmed for hazard will be activated
The alarm relay is not
activated
Silenced alarms are not
resounded
Timers are not started
Store event in history bufferActivate appropriate LED on the N-ANN-LED annunciator
(required for this application)
Hazard conditions latch.
4.9 Medical Alert Condition Operation
Medical alert operation is:
not intended for nurse call stations (applications) per UL1069.
not intended for signaling professional medical staff.
to be used for summoning security guards or other trained personnel within the facility
intended for Manual activation.
Medical Alert Condition operation will initiate the following events:
The piezo sounder ¼ second On, ¼ second Off
The LCD displays a medical alert message along with the device name, type, adjective/noun,
associated zones and time/date
Communicate the medical alert condition to the Central Station (if the default event code has
been changed from 000 to a reportable event code)
Relays programmed for medical alert will be activated
The alarm relay is not
activated
Silenced alarms are not
resounded
Timers are not started
Store event in history bufferActivate appropriate LED on the N-ANN-LED annunciator
(required for this application)
Medical alert conditions latch.