SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012 123
Read Status Operating Instructions
4.19.4 System Settings
Pressing 1 while viewing Read Status Screen #2 will display the following screens:
The operator can view the system settings options that have been programmed into the FACP.
4.19.5 Timers
Pressing 2 while Read Status Screen #2 will display the following screen:
These screens allow the operator to view the various timer settings.
READ STATUS
1=SYSTEM SETTINGS
2=TIMERS
3=DAYLIGHT SAVINGS
Read Status Screen #2
SYSTEM SETTINGS
TROUBLE REMIND NO
CANADIAN OPTION OFF
CHRGR DISABLE NO
SYSTEM SETTINGS
USER BANNER:
XXX XXXXX XXXX XXXX
READ STATUS
1=SYSTEM SETTINGS
2=TIMERS
3=DAYLIGHT SAVINGS
Read Status Screen #2
TIMERS
PAS DELAY 120
PRE SIGNAL 120
WATERFLOW DELAY 0
TIMERS
AC LOSS DELAY 2