SFP-5UD & SFP-10UD Series Manual— P/N 52879:C1 2/24/2011 157
N-ANN-LED Annunciator Installation for Canadian Applications Canadian Application
Notes:
1. Relays 1 and 2 on the N-ANN-RLY must be programmed for latching alarm activation.
2. Relays 3 and 4 on the N-ANN-RLY must be programmed for non-latching trouble activation.
3. Relays 5 and 6 on the N-ANN-RLY must be programmed for supervisory activation with
latching/non-latching set in accordance with the local AHJ.
4. The N-ANN-RLY must be mounted inside the FACP cabinet.
5. Refer to the N-ANN-RLY Document #53318 for installation instructions.
Figure F.2 Alternate Transmission for Alarm, Trouble, and Supervisory Signals
FACP
N-ANN-RLY
+
ALARM
-
+
TROUBLE
-
+
SUPERVISORY
-
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
Relay 1
TB2
Relay 2
TB2
Relay 4
TB4
Relay 6
TB5
Relay 3
TB4
Relay 5
TB5
To Remote Station Receiver
TB9
Non-resettable
Aux Power
2
1
-
+