SFP-5UD & SFP-10UD Series Manual— P/N 52879:C1 2/24/2011 157
N-ANN-LED Annunciator Installation for Canadian Applications Canadian Application
Notes:
1. Relays 1 and 2 on the N-ANN-RLY must be programmed for latching alarm activation.
2. Relays 3 and 4 on the N-ANN-RLY must be programmed for non-latching trouble activation.
3. Relays 5 and 6 on the N-ANN-RLY must be programmed for supervisory activation with
latching/non-latching set in accordance with the local AHJ.
4. The N-ANN-RLY must be mounted inside the FACP cabinet.
5. Refer to the N-ANN-RLY Document #53318 for installation instructions.
Figure F.2 Alternate Transmission for Alarm, Trouble, and Supervisory Signals