SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012 19
Specifications Product Description
The following figure illustrates the maximum current that is possible for each major panel output
circuit and the total current available from the FACP with the FLPS-7 power supply. This applies
to the SFP-5UDC, SFP-10UD, SFP-10UDE, and SFP-10UDC.
Figure 1.2 Current Availability with FACP and FLPS-7 Power Supply
powerdistmrp.wmf
Refer to the battery calculations section for additional information.
Standby
1.0 amp max
per panel
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
0.5 amp max
per circuit
0.5 amp max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
Alarm
7.0 amps
max
per panel
Primary
ANN-BUS
Standby
1.0 amp max
per panel
0.5 amp max
per circuit
0.5 amp max
per circuit
ANN-SEC
Option Card