SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012 63
Master Programming Level Programming
The following examples show the editing of Input Zone 1:
Enable/Disable Zone
To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2. Each
press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is
selected, the zone will be disabled by the control panel, preventing the circuit from reporting alarms
and troubles to the panel. The control panel LCD will display the zone which has been disabled
and FACP will turn on the Trouble LED.
Type
To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone
Screen #2. This will cause the control panel to display the following Zone Type Screen:
INPUT ZONE 1
1=ENABLED YES
2=TYPE PULL STATION
3=VERIFICATION NO
Edit Input Zone Screen #2
INPUT ZONE 1
1=PAS/PRE-SIG DELAY
NO DELAY
Edit Input Zone Screen #3
Edit Input Zone Screen #5
INPUT ZONE 1
1=ADJECTIVE/NOUN
2=DESCRIPTION
********************
INPUT ZONE 1
1=FREEZE SUPV. NO
2=ACC MSG# 2
Edit Input Zone Screen #4
INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
ZONE TYPE
1=PULL STATION
2=WATERFLOW
3=WATERFLOW NS
Zone Type Screen #1