96 SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012
Programming Master Programming Level
Ademco Contact ID Format - Secondary Central Station Phone Number
The information shown in Table 3.5 is automatically programmed for the Secondary Central Sta-
tion phone number Event Codes when Ademco Contact ID Format is selected. To disable event
reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to dis-
able it. (Enter must be pressed to save the selection. Pressing Escape will not save the selection).
Event Description
Event Code Settings
Active
Secondary # Zone 1 - 10 Alarm 115
Secondary # Zone 1 - 10 Disabled 570
Secondary # Drill 604
Secondary # AC Fault 301
Secondary # Zone 1 - 10 Fault 380
Secondary # Zone 1 - 10 Dirty 380
Secondary # Earth Fault 310
Secondary # Low Battery Fault 302
Secondary # No Battery Fault 311
Secondary # Telco Primary Line Fault 351
Secondary # Telco Secondary Line Fault 352
Secondary # NAC #1 Fault 321
Secondary # NAC #2 Fault 322
Secondary # NAC #3 Fault 326
Secondary # NAC #4 Fault 327
Secondary # NAC #1 Disable 521
Secondary # NAC #2 Disable 522
Secondary # NAC #3 Disable 526
Secondary # NAC #4 Disable 527
Secondary # Charger Fault 300
Secondary # Comm Trouble Primary # 354
Secondary # Comm Trouble Secondary # 354
Secondary # Printer Fault 336
Secondary # ANN-BUS Fault 330
Secondary # Option Card Fault 333
Secondary # CS CALC Fault 304
Secondary # System Off Normal 308
Secondary # System Test Message 602
Secondary # System Abnormal Test Message 608
Secondary # Upload/Download Request 411
Secondary # Upload Successful 416
Secondary # Download Successful 412
Secondary # Upload/Download Failed 413
Secondary # Voice EVAC Fault 330
Secondary # Power Supply Sync fault 300
Table 3.5 Ademco Contact ID Secondary # Event Codes