Section 7 - System Programming
711
QUESTION 09
MISCELLANEOUS SYSTEM OPTIONS DEFAULT = 2C06
There are 4 locations (L1-L4) for system timing and system options, as follows:
Question 09 L1
Entry Delay 2 Default = 2
Using the table in Question 8, Location 1 to determine valid choices, enter the desired entry delay time
for zones 4-8. If zones 4-8 are delay zones, then they follow entry delay 2. For UL applications,
the maximum entry delay shall not exceed 45 seconds.
Question 09, L2
Remote Communications Ring Count Default = C
Selecting from the choices below, enter a digit in Location L2.
Digit
REMOTE COMMUNICATIONS
RING COUNT
Digit
REMOTE COMMUNICATIONS
RING COUNT
0 NONE (Remote Communications Disabled) 8 8 RINGS
1 1 RING 9 9 RINGS
2 2 RINGS A 10 RINGS
3 3 RINGS B 11 RINGS
4 4 RINGS C 12 RINGS
5 5 RINGS D 13 RINGS
6 6 RINGS E 14 RINGS
7 7 RINGS F 15 RINGS
REMOTE COMMUNICATIONS RING COUNT - is the number of rings required for the control
panel to pick up and begin a remote communications session. Select a value that does not interfere with
normal operation of the panel. The default value is 12 rings.
NOTE: A value of 0 means that remote connect is disabled.
Question 09, L3
CS Test Time Interval Default = 0
CS TEST TIME INTERVAL CS TEST RESET BY
Digit
24 HOURS WEEKLY 27 DAYS 60 DAYS 90 DAYS TIME EVENT
0 NONE (CS TEST DISABLED)
1
9
9
2
9
9
3
9
9
4
9
9
5
9 9
9
9
9
A
9
9
B
9
9
C
9
9
D
9
9