Model SK-5208 Fire Control/Communicator Installation and Operation Manual
3-8 P/N 151204
* Use next size battery with capacity greater than required.
3.6.3 Maximum Battery Standby Load
Table 3-3 shows the maximum battery standby load for the SK-5208 based on 24 and 60 hours
of standby. The standby load calculations of line D in the Current Draw Calculation
Worksheet (Table 3-2) must be less than the number shown in Table 3-3 for the battery size
used and standby hours required.
Batteries larger then 18 AH will not fit into the SK-5208 cabinet and must be housed in the
RBB remote battery box cabinet. See Section 3.8 for battery installation.
* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter
(DACT).
Table 3-3: Maximum Battery Standby Load
Rechargeable Battery Size
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
7 AH 270 mA 105 mA
12 AH 475 mA 190 mA
18 AH 685 mA 270 mA
35 AH 1.1 A 450 mA
Warning!
Silent Knight does not support the use of batteries smaller than those listed in Table 3-3. If you use a battery too
small for the installation, the system could overload the battery resulting in the installation having less than the
required 24 hours standby power. Use Table 3-2 to calculate the correct battery amperes/hour rating needed for
your installation.