Model SK-5208 Fire Control/Communicator Installation and Operation Manual
3-22 P/N 151204
3.14.2.2 Wiring the SK-5235
Follow these steps to properly wire the SK-5235 to the control panel.
1. Remove power from the control panel.
2. Wire the SK-5235s as shown in Figure 3-12.
3. Set the ID number. See Table 3-5.
Note: The ID number of 7 is reserved for the built-in touchpad on the SK-5208.
4. Reapply power the the control panel.
When the annunciator powers up, it will display its ID code and current status of the panel.
Figure 3-12 Model SK-5235 Connection
Note: Each 5235 touchpad can be individually supervised. See Section 4.2.2 for programming touchpads as
supervised.
ID DIP switches
1
2
3
4
Supervised
Power Limited
Class B