Control Panel Installation
P/N 151204 3-31
3.14.4.2 Mounting Instructions
The SK-5217 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190
accessory cabinet.
Mounting the SK-5217 into SK-5208 Cabinet
Follow these steps to properly mount the SK-5217 zone expander into the SK-5208 cabinet:
1. Remove power from the control panel.
2. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-22.
Figure 3-22 Installing the SK-5217 Into the SK-5208 Cabinet
3. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19.
4. Wire the zone inputs to the zone expander as shown in Figure 3-20.
5. Set the ID code (see Section 3.14.1).
If ID code 1 is selected the SK-5217 will input zones 11 - 20.
If ID code 2 is selected the SK-5217 will input zones 21 - 30.
6. Reconnect power to the control panel.
firealarmresources.com