Model SK-5208 Fire Control/Communicator Installation and Operation Manual
6-4 P/N 151204
6.2.1 Default Settings for 3/1 Format
Table 6-3 displays the default settings which are set in the Misc. Reporting section of
Programming.
Table 6-3: Default Settings for 3/1 Format
Water Alarm Restore 1-30 WH1-WH30 AR1 - AR0 Alarm Restore Code 3 154 001 - 3 154 030
Water Trouble Restore 1-30 WJ1-WJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030
Water Trouble 1-30 WT1-WT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030
Water Unbypass 1-30 WU1-WU30 R1 - R0 Restore Code 3 570 001 - 3 570 030
Communications Failure Line #1 YC1 T1 Trouble Code 1 354 001
Communications Restore Line #1 YK1 R1 Restore Code 3 354 001
Communications Failure Line #2 YC2 T2 Trouble Code 1 354 002
Communications Restore Line #2 YK2 R2 Restore Code 3 354 002
System Battery Restore YR0 R0 Restore Code 3 302 000
System Battery Trouble YT0 T0 Trouble Code 1 302 000
Cold Alarm 1-30 ZA1-ZA30 A1 - A0 Alarm Code 1 153 001 - 1 153 030
Cold Bypass 1-30 ZB1-ZB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030
Cold Alarm Restore 1-30 ZH1-ZH30 AR1 - AR0 Alarm Restore Code 3 153 001 - 3 153 030
Cold Trouble Restore 1-30 ZJ1-ZJ30 R1 - R0 Restore Code 2 370 001 - 3 370 030
Cold Trouble 1-30 ZT1-ZT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030
Cold Unbypass 1-30 ZU1-ZU30 R1 - R0 Restore Code 3 570 001 - 3 570 030
Programming
Option
Menu Item Choices Default Comments
Misc Reporting
Test Time 00:00 - 23:59 12:00
Selects the time of day the control will send an
automatic test signal to a central station receiver.
AC Delay 0-30 Hours 2
Selects the delay time (in hours) before the control
will report an AC power loss to the central station.
Report Walk Test
No
No zone information will be reported just test
begin and test end.
By Zone
Test begin, test end, and all events in between will
be reported to central station.
*3/1 Alarm
0 - 9
* Event code for 3/1
and 4/2 reporting
formats.
0
Alarms for Fire, Waterflow, Undefined, Heat,
Cold, and Water events.
*3/1 Alarm Rst 2
Alarms restores for Fire, Waterflow, Undefined,
Heat, Cold, and Water events.
*3/1 Supervisory 6 Sprinkler supervisories.
*3/1 Restore 7
Restore reports for Troubles, Supervisories, and
unbypasses. The only exceptions are the restores
listed as alarm restores.
*3/1 Trouble 8
All system and zone troubles, and zone/NAC
bypasses, and NACs troubles.
*3/1 Test 9 All test events.
Table 6-2: Event and Reporting Code by Format
Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID
firealarmresources.com