Model SK-5208 Fire Control/Communicator Installation and Operation Manual
4-14 P/N 151204
4.2.11 5280 Outputs
Figure 4-13 illustrates, in more detail, the programming flow when in the SK-5280 outputs
menu.
Figure 4-13 5280 Outputs Programming Menu
If Zones 1-10 is selected then the SK-5280 will output when alarms and troubles occur for
zones 1 through 10. If Zones 11-20 is selected then SK-5280 will output when alarms and
troubles occur for zones 11 through 20. If Zones 21-30 is selected then the SK-5280 will
output when alarms and troubles occur for zones 21-30.
If System is selected then the SK-5280 will output as shown in Table 4-3 for the following
system conditions:
Table 4-3: System Outputs
SK-5280 Output
Terminal
Output For:
A1 Fire Alarm
A2 Waterflow Alarm
A3 Supervisory
A4 Aux Alarm
A5 Prealarm
A6 Trouble
A7 Communications Fail
A8 Communicating
A9 Alarm Silenced
A10 Trouble Silenced
T1 Low AC
T2 Low Battery
T3 Relay 1 Active
T4 Relay 2 Active
T5 Relay 3 Active
T6 Relay 4 Active
T7 NAC 1 Active
T8 NAC 2 Active
T9 NAC 3 Active
T10 NAC 4 Active