Control Panel Installation
P/N 151204 3-25
3.14.3.1 Mounting the SK-5280
The SK-5280 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190
accessory cabinet.
Mounting the SK-5280 into SK-5208 Cabinet
Follow these steps to properly mount the SK-5280 into the SK-5208 cabinet:
1. Remove power from the control panel.
2. Mount the SK-5280 onto the standoffs and bracket located in the cabinet. See Figure 3-15.
Figure 3-15 Installing the 5280 Into the 5208 Cabinet
3. Connect the SK-5280 to the SK-5208 control panel as shown in Figure 3-14.
4. Set the ID number (see Figure 3-13 for ID DIP switch location). See also Section 3.14.1for
information on setting ID numbers.
5. Reconnect power to the control panel.