EasyManua.ls Logo

Honeywell SILENT KNIGHT SK-5208 - Wiring Relays; Wiring Leds to Outputs

Honeywell SILENT KNIGHT SK-5208
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Panel Installation
P/N 151204 3-27
3.14.3.2 Wiring Relays
The four on-board relays can be triggered by the active low outputs. For example, the alarm
outputs can all be wired to relay 3 and the trouble outputs can be wired to relay 4
(see Figure 3-17).
C1 is the coil for the relay 1, C2 is the coil for relay 2, C3 and C4 are the coils for relays 3 and
4 respectively.
Figure 3-17 Relay Wiring on the SK-5280
Note: Figure 3-17 uses A7 and T7 to activate relays 3 and 4 as an example. However, any of the outputs can be
used to trip any of the relays.
3.14.3.3 Wiring LEDs to Outputs
The outputs (A1-A10 and T1-T10) can be used to operate LEDs used in a remote annunciator
(see Figure 3-18). Outputs A1-A10 are alarm outputs for the zones corresponding to those
outputs. For example, if the SK-5280 is programmed to output for zones 11-20, then outputs
A1-A10 will correspond with zones 11 through 20.
Outputs T1-T10 are trouble outputs for the zones corresponding to those outputs. for example,
if the SK-5280 is programmed to output for zones 21-30, then outputs T1-T10 will correspond
Relay Rating
2.5A @ 30 VDC/120 VAC
firealarmresources.com

Table of Contents

Related product manuals