MAN0878-09-EN_XLE_XLT_UserManual
A u g u s t 2 3 , 2 0 1 8 P a g e 55 | 158
Set Fkeys
The Set Fkeys Sub-Menu displays two System Settings, both of which are editable.
Fkeys: Momentary = %K1-10 bits go On & Off as F1-F10 are pressed & released
Toggle = %K1-10 bits toggle each time F1-F10 are pressed
SYS_Fn enable: Yes = Reset and all clear system functions enabled
No = Reset and all clear system functions disabled
Set Serial Ports
The Set Serial Ports Sub-Menu displays three System Settings; all of which are editable, and one
optional item. For the Dflt Pgm Port System Setting, only MJ1-232 can be selected, unless either
an Ethernet (XEC) or a Modem (XMC) COM module is installed. Also, the Set Ethernet (Enet)
item only appears if an Ethernet COM module is installed.
Dflt Pgm Port: MJ1-232 = MJ1 RS232 port is the default programming port
Enet = Ethernet COM module is the default programming port
Modem = Modem COM module is the default programming port
MJ1 RS485 Bias: No = MJ1 RS485 bias resistors are not switched in
Yes = MJ1 RS485 bias resistors are switched in
MJ2 RS485 Bias: No = MJ2 RS485 bias resistors are not switched in
Yes = MJ2 RS485 bias resistors are switched in
Set Ethernet (Enet) = Select and press Enter to setup the Ethernet COM module
Set Ethernet (Enet) (for units older than Rev TA)
The Set Ethernet (Enet) Sub-Menu displays three System Settings, all of which are editable. The
values shown below are the default values.
NOTE: If Gtwy is set to 0.0.0.0, Ethernet communication will be confined to the local network.
Addr: 192.168.254.128 = IP Address for installed Ethernet COM module
Mask: 255.255.255.0 = Net Mask for installed Ethernet COM module
Gtwy: 0.0.0.0 = Gateway device IP Address for installed Ethernet COM module