B-3
Specifications
The following tables contain the environmental, electrical, and physical specifications for the HP3000 
and HP 9000 Enterprise Server systems.
Table B-9. Environmental Specifications.
Description Specification
HP 9000 - 
K100, K200, K210, K220,
K400, K410, & K420
HP 3000 - 929KS, 939KS, 959KS,
969KS/x00, & 969KS/x20
HP 9000 - K250, K260, K450, & K460
HP 3000 - 979KS
Operating Temperature
5° to 40°
 
C (41° to 104°
 
F) 5° to 40°
 
C (41° to 104°
 
F)
Non-operating Temperature
-40° to 65°
 
C (-40° to 149°
 
F)
(without internal tape media device)
-40° to 45°
 
C (-40° to 113°
 
F)
(with internal tape media device)
-40° to 65°
 
C (-40° to 149°
 
F)
(without internal tape media device)
-40° to 45°
 
C (-40° to 113°
 
F)
(with internal tape media device)
Temperature Rate of Change
20°
 
C (36°
 
F)/hr. 
(with no internal tape media device)
10°
 
C (18°
 
F)/hr. 
(with internal tape media device)
20°
 
C (36°
 
F)/hr. 
(with no internal tape media device)
10°
 
C (18°
 
F)/hr. 
(with internal tape media device)
Over Temperature 1st 
Warning
35° C (95° F) 35° C (95° F)
Over Temperature 2nd 
Warning
40° C (104° F) 40° C (104° F)
Over Temperature Shutdown 43° C (109° F) 43° C (109° F)
Operating Humidity Range 15% to 80% Relative Humidity 
(Non-condensing at 26°
 
C (79°
 
F) with 
internal tape media device)
15% to 80% Relative Humidity 
(Non-condensing at 22°
 
C (72°
 
F) with 
internal tape media device)
Non-operating Humidity 
Range
5% to 90% Relative Humidity 
(Non-condensing at 65°
 
C (149°
 
F)
5% to 80% Relative Humidity 
(Non-condensing at 65°
 
C (149°
 
F)
Relative Humidity Change 
Rate
30% Relative Humidity Change/Hr 
(Maximum)
30% Relative Humidity Change/Hr 
(Maximum)