B-24
Table B-25. 
A2998A PowerTrust UPS Specifications.
Description Specification
Electrical Specifications:
AC Line Input:
Rated Voltage 200 - 240 VAC 50/60 Hz (300 VAC Max)
Frequency Ranges 47 - 53 Hz or 57 - 63 Hz
Rated Current 20.0 Amps (30 Amp max. branch circuit overcurrent protection)
AC Output:
Output VAC
(On Line Power)
Same as line input power
Rated Power Up to 3000 VA
Up to 3000 Watts (Power factor of 1.0 assumed)
Loading(% of rated power in
Normal (not Bypass) mode):
0 - 110%
110 - 130%
> 130%
UPS will operate indefinitely
UPS will operate for up to 5 minutes
UPS will operate for <10 seconds
Voltage Normal
Mode
223 - 237 VAC
47 - 53 Hz or 57 - 63 Hz
Current:
Maximum
Supported Load
Chrst Factor
13 Amps (rms)
<
3 Amps peak/Amps rms)
Waveshape True sine wave with < 5% total harmonic distortion
Transfer Time AC Failure - <
 10 msec to switch to battery power
Input disconnect delay - 4 msec
AC Restored -20 Sec delay returning to phase lock with input AC
Phasing Phase locked to within 5º of input utility AC
Safety Agency Approvals UL, CSA, and TUV
Fuse 20 Amp/250 VAC UL Listed Time Delay (Slow-Blow) Type