B-25
Battery:
Type Maintenance-free, sealed, lead-acid type (20 Amp/Hour)
Nominal open
circuit voltage 120 VDC
Battery Runtime
20º C (68º F) or above
New battery
15 minutes over battery lifetime
15 minutes over full temperature range
Battery Recharge
Time
< 14 Hours (UPS OFF) (at 20º C (68º F) or above)
< 24 Hours (UPS Operating) (at 20º C (68º F) or above)
Optimum Battery
Lifetime 
at <
 25º C (< 77º F) 4 years
Environmental Specifications
Operating 
Temperature
5º to 40º C (41º to 104º F)
15% - 80% relative humidity (non-condensing)
Storage Temperature -30º to 50º C (-20º to 122º F) Battery life is shortened severely
when temperature exceeds 25º C (77º F) for extended periods.
5% - 80% relative humidity (non-condensing)
Operating Altitude 3000 meters (10,000 ft.)
Storage Altitude 4572 meters (15,000 ft.)
Table B-25. 
A2998A PowerTrust UPS Specifications. (Continued)
Description Specification