UPS operations  28 
Available settings  Parameter   Associated LED  Explanation (when LED is illuminated) 
Wiring Fault Setting  Wiring Fault  Utility (green) 
Audible alarm sounds when ground is 
missing or line and neutral connections are 
reversed 
ERM Setting  0 ERMs 
0% to 25% load 
(green) 
UPS is configured for no attached ERMs 
(factory default) 
 
1 ERM 
26% to 50% 
load (green) 
UPS is configured for 1 attached ERM 
 
2 ERMs 
51% to 75% 
load (green) 
UPS is configured for 2 attached ERMs 
 
To change the UPS configuration parameters: 
1.  Place the UPS in Configure mode (on page 27).  
The LEDs associated with the currently configured parameters illuminate. A flashing green cursor 
indicates where you are in the configuration process as you scroll through the available settings. 
2.  To change the nominal voltage, press the On button to advance the cursor to the LED associated with 
the appropriate nominal voltage parameter. The selected voltage configuration LED flashes. 
3.  Press the Standby button to select the nominal voltage configuration. The LED associated with the old 
input voltage parameter turns off, and the LED associated with the new input voltage parameter 
illuminates solid green. 
 NOTE:  Only one nominal utility voltage can be configured. When setting voltage configuration parameters, 
selecting an On value for any one parameter automatically sets the other possibilities to Off. 
4.  To enable the Wiring Fault parameter, press the On button to advance the cursor to the Utility LED, 
then press the Standby button. The LED illuminates solid green. This parameter is disabled by default, 
and should only be enabled for line-to-neutral connections. Enabling this feature for line-to-line power 
sources causes a false alarm. 
5.  To configure the UPS for the number of connected ERMs, press the On button to advance the cursor 
to the load LED associated with the number of ERMs attached to the UPS. 
6.  Press the Standby button to select the appropriate ERM configuration. The associated LED illuminates 
solid green. 
7.  To save the configuration settings and exit Configure mode, press the Test/Alarm Reset button. 
 NOTE:  Configure mode times out after 2 minutes. If the Test/Alarm Reset button has not been pressed, any 
new selections are not saved. 
 
Testing the LEDs 
To test the LEDs, press and hold the Test/Alarm Reset button for 3 seconds. 
 
Silencing an audible alarm 
To silence an alarm, press the Test/Alarm Reset button ("UPS front panel controls" on page 7). 
 IMPORTANT: