11. Install the air bale.
12. Install the access panel.
13. Install the server into the rack.
14. Connect all peripheral cables to the server.
15. Connect each power cord to the server.
16. Connect each power cord to the power source.
17. Power up the server.
18. If Intel Xeon Gold 6244 Processors are installed, enable the enhanced cooling function.
19. If removed,
install the front bezel.
The installation is complete.
Enable the enhanced cooling function
The server generates more heat when Intel Xeon Gold 6244 Processor is installed. To maintain proper cooling, increase
the fan speed.
Procedure
1.
From the System Utilities screen, select System Configuration > BIOS/Platform Configuration (RBSU) > Advanced
Options > Fan and Thermal Options > Thermal Configuration.
2.
Select Enhanced CPU Cooling.
3.
Save your setting.
Fan option
Fan population guidelines
The number of fans installed in the server determines fan redundancy.
Configuration
Fan redundancy Bay 1 Bay 2 Bay 3 Bay 4 Bay 5 Bay 6
One processor without
rear 2-SFF drives
installed
No Blank Blank Blank Fan Fan Fan
One processor without
rear 2-SFF drives
installed
Yes Blank Fan Blank Fan Fan Fan
One processor with rear
2-SFF drives installed
No Blank Fan Fan Fan Fan Fan
Table Continued
Hardware options installation 79