Shenzhen Hpmont Technology Co., Ltd Appendix A Parameters
HD20 Series Inverters User Manual 133
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
2
F13.05 Rated speed of motor 2 124000rpm 1500rpm 1rpm ×
F13.06 Power factor of motor 2 0.0011.000
Dependent
on inverter
model
0.001 ×
F13.07
Parameter auto-tuning of
motor 2
0: Auto-tuning is disabled
1: Stationary auto-tuning
2: Rotary auto-tuning
0 1 ×
F13.08
Stator resistance of motor
2
0.0099.99Ω
Dependent
on inverter
model
0.01Ω ×
F13.09
Rotor resistance of motor
2
0.0099.99Ω 0.01Ω ×
F13.10
Leakage inductance of
motor 2
09999mH 1mH ×
F13.11
Mutual inductance of
motor 2
05000mH 1mH ×
F13.12
Idling exciting current of
motor 2
0.0099.99A 0.01A ×
F13.13 Reserved
F13.14 Reserved
F13.15 Reserved
F13.16
V/f curve selection of
motor 2
0: Line
1: Square curve
2: 1.2 exponential curve
3: 1.7 exponential curve
4: User-defined curve
0 1 ×
F13.17
V/f frequency value F3 of
motor 2
F13.19F13.04 0.00Hz 0.01Hz ×
F13.18
V/f voltage value V3 of
motor 2
F13.20F13.02 0V 1V ×
F13.19
V/f frequency value F2 of
motor 2
F13.21F13.17 0.00Hz 0.01Hz ×
F13.20
V/f voltage value V2 of
motor 2
F13.22F13.18 0V 1V ×
F13.21
V/f frequency value F1 of
motor 2
0.00F13.19 0.00Hz 0.01Hz ×
F13.22
V/f voltage value V1 of
motor 2
0F13.20 0V 1V ×
F13.23 Torque boost of motor 2
0.030.0%
0.0: Auto torque boost
2.0% 0.1% ×
F13.24
Cut-off point used for
manual torque boost of
motor 2
0.050.0%F13.04 10.0% 0.1%
F13.25
Slip compensation gain of
0.0300.0% 100.0% 0.1%
A

Table of Contents

Related product manuals