Appendix C Communication Protocol Shenzhen Hpmont Technology Co., Ltd
―172― HD30 Series Inverters User Manual
Corresponding answer frame:
Address Parameter Register address Register content Checksum
0x02 0x41 0x32 0x00 0x10 0x08 0x3f 0x48
8. Coast to stop command of Slave 2
Address Parameter Register address Register content Checksum
0x02 0x41 0x32 0x00 0x10 0x10 0x3f 0x42
Corresponding answer frame:
Address Parameter Register address Register content Checksum
0x02 0x41 0x32 0x00 0x10 0x10 0x3f 0x42
9. External fault stop control of Slave 2 via communication (E0024 has fault)
Address Parameter Register address Register content Checksum
0x02 0x41 0x32 0x00 0x10 0x20 0x3f 0x56
Corresponding answer frame:
Address Parameter Register address Register content Checksum
0x02 0x41 0x32 0x00 0x10 0x20 0x3f 0x56
10. Fault reset of Slave 2
Address Parameter Register address Register content Checksum
0x02 0x41 0x32 0x00 0x11 0x00 0x3f 0x1E
Corresponding answer frame:
Address Parameter Register address Register content Checksum
0x02 0x41 0x32 0x00 0x11 0x00 0x3f 0x1E
11. Function parameter management and read the lower limit of F02.03
Address Parameter Subfunction code Data Checksum
0x02 0x42 0x00 0x01 0x02 0x03 0x69 0x57
Corresponding answer frame:
Address Parameter Subfunction code Data Checksum
0x02 0x42 0x00 0x01 0x00 0x00 0x0d 0xcf