Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd
58 HD30 Series Inverters User Manual
6.2.2 Group F01 Protection of Parameters
No. Name Description Range
factory setting
F01.00 Users password 00000
65535
00000
XXXXX: To enable the password protection function, set any non-zero number as the password.
Once the password is set, if you want to change any parameter you must input correct password.
Otherwise, all the parameters cannot be changed but only read.
When input correct password, by pressing the key to exit to stop/run display status or by
detecting that there is no press on the display panel within 5 minutes, the user’s password will be
valid. It is necessary to input correct password if you want to change the parameters. It will restart
when there is no press on the display panel within 5 minutes.
00000: The factory setting of F01.00 is 0, namely the password protection function is disabled.
If the user unlocks the password, it means clearing the user’s password.
To unlock, change and clear the user’s password, see section 5.2.3.
F01.01 Menu mode selection 0,1
0
0: Full menu mode. All function parameters can be displayed in this menu.
1: Checking menu mode. Only different from factory setting parameters can be displayed.
F01.02 Function code parameter initialization 0,1
0
0: No operation. The inverter is in regular parameter read/write status.
Whether can change the parameter it depends on the users password status and the actual
operating conditions.
1: Restore to factory settings. Except F01.00, F01.02, F01.03, Group F08, F13.01F13.15,
F19.24F19.25, F20.21F20.37 and Group y.
Operation steps: If set F01.02 = 1, press to ensure and the parameters are restored to
factory settings. The display panel dispalys “rESEt”. Then the display panel will display
parameters in stop status after finish restoring to factory setting.
2: Download the display panel EEPROM parameter 1 to the current function code settings.
3: Download the display panel EEPROM parameter 2 to the current function code settings.
4: Clear fault information. The fault history of F20.21F20.37 will be clear.
F01.03 Display panel EEPROM parameter initialization 0
2
0
0: No operation. The inverter is in regular parameter read/write status.
1: Upload the current function code settings to the display panel EEPROM parameter 1.
2: Upload the current function code settings to the display panel EEPROM parameter 2.
Note: F01.00, F01.02, F01.03, Group F08, F13.01
F13.15, F19.24
F19.25, F20.21
F20.37 and
Group y do not upload or download.
PRG

Table of Contents

Other manuals for hpmont HD30 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the hpmont HD30 Series and is the answer not in the manual?

hpmont HD30 Series Specifications

General IconGeneral
Brandhpmont
ModelHD30 Series
CategoryInverter
LanguageEnglish

Related product manuals