EasyManuals Logo

HT EASYTEST COMBI519 User Manual

HT EASYTEST COMBI519
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
EASYTEST-COMBI519
EN - 14
6. OPERATING INSTRUCTIONS
6.1. AUTO: AUTOMATIC TEST SEQUENCE (RA , RCD, M)
This function allows performing the following measurements in an automatic sequence:
Overall earth resistance without causing the RCD’s tripping (Ra )
Tripping current and tripping time of General RCDs type A ( ), AC ( ) or B ( )
Insulation resistance with test voltages 50, 100, 250, 500, 1000 VDC
CAUTION
Some combinations of test parameters could be unavailable in compliance with
the technical specifications of the instrument and the RCD tables (see § 10.1 –
empty cells of RCD tables mean unavailable situations)
CAUTION
Testing the RCD’s tripping time causes the RCD’s tripping. Therefore, check
that there are NO users or loads connected downstream of the RCD
being tested which could be damaged by a system downtime. Disconnect
all loads connected downstream of the RCD as they could produce leakage
currents further to those produced by the instrument, thus invalidating the
results of the test.
Fig. 4: Instrument connection through mains plug
Fig. 5: Instrument connection by means of single cables and remote switch probe

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HT EASYTEST COMBI519 and is the answer not in the manual?

HT EASYTEST COMBI519 Specifications

General IconGeneral
BrandHT
ModelEASYTEST COMBI519
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals